Regional validity

Scope

solid wood construction
Cross-section of standard configuration

solid wood construction
Standard configuration

Register of building materials used for this application, cross-section (from outside to inside)

Thickness [mm] Building material Thermal performance Reaction to fire­
λ μ min – max ρ c
A 12,5 gypsum fibre board 0,320 21 1000 1,100 A2
A 12,5 gypsum plaster board type DF or 0,250 10 800 1,050 A2
B 70,0 spruce wood batten mounted on resilient clips (60/60; e=625) 0,120 50 450 1,600 D
C 50,0 mineral wool [040; 13] 0,040 1 13 1,030 A2
D cross laminated timber 0,130 50 500 1,600 D
E impact sound absorbing subflooring MW-T packed 0,035 1 68 1,030 A1
F cross laminated timber 0,130 50 500 1,600 D
G 50,0 mineral wool [040; 13] 0,040 1 13 1,030 A2
H 70,0 spruce wood batten mounted on resilient clips (60/60; e=625) 0,120 50 450 1,600 D
I 12,5 gypsum fibre board 0,320 21 1000 1,100 A2
I 12,5 gypsum plaster board type DF or 0,250 10 800 1,050 A2

Variations of building components

Thickness of layer Note Fire performance Thermal performance Acoustic performance Eco Sustainability Mass
Thickness [mm] Building material Σ REI U [W/(m²K)] Diffusion Rw (C,Ctr) OI3Kon m [kg/m²]
twmxxo06a-00 D
E
F
78,0
30,0
78,0
cross laminated timber
impact sound absorbing subflooring MW-T
cross laminated timber
331,0 D and F: (e.g. d ≥ 78mm; 3-ply at least, surface layer at least 25mm) 60 0,21 adequate 59 73,00 107,0
twmxxo06a-01 D
E
F
97,0
40,0
97,0
cross laminated timber
impact sound absorbing subflooring MW-T
cross laminated timber
399,0 60 0,20 adequate 61 (-4,-11) 126,1

Last update 28.06.2018/hfa.plb