Scope

Building physical assessment

Fire performance REI from inside
REI from outside
60
90
maximum ceiling height = 3 m; maximum load Ed,fi = 19,2 kN/m; REI 90 from the outside  
Classified by HFA  
Thermal performance U 0,12 W/(m2K)
Diffusion adequate
Calculated by HFA  
Acoustic performance Rw (C;Ctr) 52 dB
Ln,w (Cl)
Rating by TGM  
Mass per unit area m 79,5 kg/m2
 
timber frame construction
Cross-section of standard configuration
timber frame construction
Standard configuration

Register of building materials used for this application, cross-section (from outside to inside)

Thickness [mm] Building material Thermal performance Reaction to fire­klasse EN
λ μ min – max ρ c
A 6,0 plaster 1,000 10-35 2000 1,130 A1
B 100,0 MW-PT FKD-S C2 [036; R=110] 0,036 1 110 1,030 A1
C 15,0 OSB 0,130 200 600 1,700 D
D 200,0 construction timber (60/..; e=625) 0,120 50 450 1,600 D
E 200,0 glass wool UNIFIT [037; R=14] 0,037 1 14 1,030 A1
F vapour barrier sd≥ 14m
G 50,0 Heraklith BM 0,090 2-5 370 2,000 B
H 15,0 plaster 0,700 10 1300 1,000 A1

Ecological rating (per m2 construction area)

Database ecoinvent

Built-in renewable materials 30,8 kg
Share of renewable materials of total weight 38,43 %
Global warming potential (GWP-T) 9,650 kgCO2Äqv.
Energy use of Primary Energy 794,0 MJ
Share of renewable Primary Energy 11,8 %
∑ΔOI3 60,8
Calculated by HFA  

Global warming potential Share of renewable Primary Energy Resources
Lifecycle
Phase
GWP-F
[kgCO2Äqv.]
GWP-B
[kgCO2Äqv.]
GWP-T
[kgCO2Äqv.]
PERE
[MJ]
PERM
[MJ]
PERT
[MJ]
PENRE
[MJ]
PENRM
[MJ]
PENRT
[MJ]
AP
[kgSO2Äqv.]
EP
[kgPO4Äqv.]
ODP
[kgR11Äqv.]
POCP
[kgEthenÄqv.]
A1 - A3 50,153 -40,503 9,650 93,379 403,787 497,166 700,583 15,758 716,341 0,265 0,092 3.4974829E-6 0,074

Source: Knauf Insulation GmbH

Last update 02.08.2023/hfa.eco2soft