Scope

Building physical assessment

Fire performance REI 90
EI 90 (for the whole construction); maximum ceiling height = 3 m; maximum load Ed,fi = x kN/m  
Classified by HFA  
Thermal performance U 0,18 W/(m2K)
Diffusion
Calculated by HFA  
Acoustic performance Rw (C;Ctr) 68 dB
Ln,w (Cl)
The acoustic insulation assessment is based on a length-related flow resistance of r≥5 kPa.s/m². If this value is lower for the insulation material used, the Rw value is reduced by 3dB.  
Rating by TGM  
Mass per unit area m 73,0 kg/m2
 
timber frame construction
Cross-section of standard configuration

Register of building materials used for this application, cross-section (from outside to inside)

Thickness [mm] Building material Thermal performance Reaction to fire­klasse EN
λ μ min – max ρ c
A 30,0 Rigips Riduro 2x...mm 0,250 4-10 1000 1,050 A2
B 100,0 construction timber (60/..; e=625) 0,120 50 450 1,600 D
C 100,0 ISOVER Multi-Kombi Holzrahmenfilz 0,033 1 11 1,030 A1
D 10,0 mineral wool [040; ≥16; <1000°C] 0,040 1 16 1,030 A1
E 100,0 construction timber (60/..; e=625) 0,120 50 450 1,600 D
F 100,0 ISOVER Multi-Kombi Holzrahmenfilz 0,033 1 11 1,030 A1
G 30,0 Rigips Riduro 2x...mm 0,250 4-10 1000 1,050 A2

Ecological rating (per m2 construction area)

Database ecoinvent

Built-in renewable materials 12,1 kg
Share of renewable materials of total weight 16,60 %
Global warming potential (GWP-T) 6,446 kgCO2Äqv.
Energy use of Primary Energy 467,3 MJ
Share of renewable Primary Energy 11,8 %
∑ΔOI3 27,5
Calculated by IBO  

Global warming potential Share of renewable Primary Energy Resources
Lifecycle
Phase
GWP-F
[kgCO2Äqv.]
GWP-B
[kgCO2Äqv.]
GWP-T
[kgCO2Äqv.]
PERE
[MJ]
PERM
[MJ]
PERT
[MJ]
PENRE
[MJ]
PENRM
[MJ]
PENRT
[MJ]
AP
[kgSO2Äqv.]
EP
[kgPO4Äqv.]
ODP
[kgR11Äqv.]
POCP
[kgEthenÄqv.]
A1 - A3 24,111 -17,666 6,446 55,270 191,189 246,459 412,055 0,978 413,033 0,095 0,043 2.7987544E-6 0,014

Source: Saint-Gobain Austria GmbH

Last update 02.08.2023/hfa.eco2soft